Select Proper Hand-eye Calibration Process

You are currently viewing the documentation for version 1.7.5. To access documentation for other versions, click the "Switch Version" button located in the upper-right corner of the page.

■ To use the latest version, visit the Mech-Mind Download Center to download it.

■ If you're unsure about the version of the product you are using, please contact Mech-Mind Technical Support for assistance.

Hand-eye calibration establishes the transformation relationship between the camera and robot reference frames. With this relationship, the object pose determined by the vision system can be transformed into that in the robot reference frame, which guides the robot to perform its tasks. The accuracy of hand-eye calibration results affects the accuracy of robot picking.

After the Mech-Mind Vision System is constructed, you can start the hand-eye calibration. In addition, you need to perform hand-eye calibration again in any of the following conditions:

  • The camera moves in reference to the robot base (camera mounted using the Eye to Hand method) or flange (camera mounted using the Eye in Hand method).

  • The camera is replaced.

  • The robot is replaced.

Select the Proper Calibration Process

The calibration procedures are affected by robot communication modes, camera mounting modes, calibration modes, and calibration data collection methods. Mech-Vision provides standardized calibration procedures for various scenarios, helping you calibrate the camera intrinsic and extrinsic parameters quickly and accurately.

For explanations of the robot communication modes, camera mounting modes, calibration modes, and calibration data collection methods, refer to the section Calibration-related Concepts.

Please follow instructions in this section to select the proper calibration process.

calibration select robot process
  1. Confirm whether the robot supports communication using Standard Interface or Master-control.

    • If yes, choose automatic calibration and proceed to Step 2.

    • If no, choose manual calibration and proceed to Step 3.

  2. Confirm the camera mounting mode for automatic calibration.

  3. Confirm the camera mounting mode for manual calibration.

If two cameras are used in a project, please perform calibration by referring to the section Hand-Eye Calibration in the Eye to Eye Scenario. If a truss robot is used in a project, please perform calibration by referring to the section Hand-Eye Calibration for Truss Robots.

We Value Your Privacy

We use cookies to provide you with the best possible experience on our website. By continuing to use the site, you acknowledge that you agree to the use of cookies. If you decline, a single cookie will be used to ensure you're not tracked or remembered when you visit this website.