HYUNDAI Calibration Program
This topic introduces the process of automatic hand-eye calibration when a HYUNDAI robot communicates with Mech-Mind Vision System through Standard Interface.communication.
Before proceeding, please make sure that Set up Standard Interface Communication with HYUNDAI has been finished. |
Select the Calibration Program
-
On the teach pendant, select Program at the upper left corner and enter the program number 9703 to open the calibration program.
-
Change the value of V500$ to the IP address of the IPC, and set the value of V500% to the port number configured in Mech-Vision.
Run the Calibration Program
-
Move the robot to the start point for the calibration.
-
Switch to AUTO mode, and press START to execute the robot program 9703. If the robot is connected successfully, the Console tab of Mech-Vision Log panel will display: Entering the calibration process, please start the calibration in Mech-Vision.
Complete Calibration in Mech-Vision
-
In Mech-Vision, click Camera Calibration (Standard) on the toolbar, or select
from the menu bar. -
Follow the instructions based on different camera mounting methods to complete the configuration.
-
If the camera is mounted in the eye-to-hand mode, please refer to Complete Automatic Calibration in the Eye to Hand Scenario.
-
If the camera is mounted in the eye-in-hand mode, please refer to Complete Automatic Calibration in the Eye in Hand Scenario.
-
If the robot does not reach the next calibration point within 60 seconds, Mech-Vision will report a timeout error and stop the calibration process. In such cases, please select and run the calibration program on the teach pendant again, and restart the calibration process in Mech-Vision. |