Failed to Call setDigitalOut of HYUNDAI_XX

You are currently viewing the documentation for the latest version (2.1.2). To access a different version, click the "Switch version" button located in the upper-right corner of the page.

■ If you are not sure which version of the product you are currently using, please feel free to contact Mech-Mind Technical Support.

Problem

During Master-Control communication, the Hyundai robot reports the error shown below at the Set DO Step in the Mech-Viz project, although no error is recorded in the log file.

faq1 1

Possible Causes

The UDP protocol used by the Hyundai robot responds relatively slowly, which may cause it to exceed the robot service timeout set in Mech-Viz.

Solutions

In the lower-right corner of Mech-Viz, click the Others tab and appropriately increase the robot service timeout, for example, to 3000 ms.

faq1 2